top of page

Short-Form System Reference Guide: Water Treatment Plants

Wally Bates
Sep 27
25 min read

Use this guide to choose a coating system by substrate, exposure and service condition. It is a selection reference, not a bid-ready specification. The full guide is below, and a PDF copy is free to download.

Download the PDF: the file is attached at the end of this page.

Questions: atlantic@tnemec.com or 484-644-5303.


Reader's Note

Use this guide to quickly select a coating or lining system by plant area, substrate, and exposure. It is a selection reference for operations, facilities/asset management, and project teams; it is not a bid-ready specification.

For bid or construction documents, use the companion CSI 3-part specification, Section 09 96 24 - High-Performance Coatings and Linings (Water Treatment), or contact ACC for project-specific guidance.

Prepared as a service by: Atlantic Coating Consultants | Wally Bates | atlantic@tnemec.com | 484-644-5303

Overview

1. Purpose

This guide summarizes water treatment plant coating and lining systems for potable-water immersion systems for steel, ductile iron and concrete (NSF/ANSI/CAN 61 and 600), tank and pipe exteriors, secondary containment, condensation mitigation, and the shared interior, exterior and resinous flooring systems used in plant buildings and support spaces.

2. How to Use This Guide

  • Start with the Quick Locator Index if you know the plant area or component. Find the applicable system in the schedule below.

  • If you know the substrate and exposure, go directly to the system tables and match the Condition and Typical Locations.

  • Use Surface Preparation, Coat Schedule, and Total Build for budgeting and work-order planning.

  • Contact ACC to confirm project-specific exposure, chemical service, surface condition, color coding, or full CSI specification requirements.

3. Basis of Design

Products scheduled herein are manufactured by Tnemec Company, Inc., and are listed as the basis of design for the performance, appearance, and warranty characteristics described. For potable-water service, confirm current NSF/ANSI/CAN 61 & 600 certification of the specific product and color at the time of specification.

4. Not Covered in This Guide

Architectural coatings for non-process administration/office spaces are summarized here only as shared systems; see the companion Architectural guide for the full set. Vehicular parking decks are not covered. Secondary containment coverage is limited to the chemicals listed in WW-C2.1; contact ACC for other chemical exposures.

5. General Application & Warranty Notes

  • Follow the current Tnemec product data sheet for substrate, ambient, dew-point, humidity, ventilation, and application requirements.

  • Verify dry film thickness during and after application. For immersion, lining, and resinous flooring work, consider a mock-up or field sample before full-scale application.

  • Comply with applicable confined-space entry, ventilation, and atmospheric-monitoring requirements for enclosed process structures.

  • Tnemec warranty terms vary by system and project; contact ACC or Tnemec to confirm applicable coverage.

Quick Locator Index

Find a system by where it goes. Confirm project-specific conditions before final selection.

Plant Area / Component

Applicable System

ADMINISTRATION / CONTROL / OFFICE BUILDING


Interior support spaces — the exterior envelope is covered in the companion Architectural guide (Section 09 96 00), not here.


Interior Walls (Gypsum Wallboard)

Gypsum board wall systems are not covered in this guide — see the companion Architectural guide (Section 09 96 00).

Resinous Flooring

100% Solids Epoxy — 1/16" Solid Color Epoxy Broadcast — Light Duty


Water-Based Epoxy — 1/16" Solid Color Epoxy Broadcast — Light Duty


100% Solids Epoxy — 1/8" Solid Color Epoxy Broadcast — Moderate Duty


Water-Based Epoxy — 1/8" Solid Color Epoxy Broadcast — Moderate Duty

RAW WATER INTAKE / PUMP STATIONS


Steel Tanks, Pipes & Equipment (Non-Immersion)

Potable Water, Steel — Tanks, Structural Steel and Equipment — Exterior, Non-Immersion


Exterior New Steel — Zinc / Epoxy / Urethane (Good)


Exterior Steel Overcoat — Epoxy Mastic / Urethane (Good)

Steel Pipe & Equipment (Immersion, Potable Water)

Potable Water, Steel — Steel Pipe — Immersion

Ductile Iron Pipe, Valves & Fittings (Immersion)

Potable Water, Steel — Ductile Iron Pipe, Valves and Fittings — Immersion

Resinous Flooring (Pump Station Dry Pit)

Urethane Cement — 1/4" Solid Color Urethane Cement — Heavy Duty

CLEARWELLS / FILTER STRUCTURES / FINISHED WATER STORAGE


Direct immersion contact with potable water — NSF/ANSI/CAN 61 & 600 systems.


Concrete Structure (Immersion, Potable Water)

Potable Water, Concrete — Cast-in-Place Concrete — 100% Solids Epoxy (Best)


Potable Water, Concrete — Cast-in-Place Concrete — High Solids Epoxy (Good)

Steel Tanks & Equipment (Immersion, Potable Water)

Potable Water, Steel — Tanks, Structural Steel and Equipment — Immersion, 100% Solids Epoxy (Best)


Potable Water, Steel — Tanks, Structural Steel and Equipment — Immersion, High Solids Epoxy (Good)

Steel Pipe (Immersion, Potable Water)

Potable Water, Steel — Steel Pipe — Immersion

Ductile Iron Pipe (Immersion)

Potable Water, Steel — Ductile Iron Pipe, Valves and Fittings — Immersion

Resinous Flooring (Below-Grade / MVT Areas)

Urethane Cement — 1/8" Solid Color Urethane Cement — Moderate/Heavy Duty

ULTRAFILTRATION / MEMBRANE TREATMENT BASINS


Concrete Basin Lining (Fiberglass-Reinforced)

A fiberglass-reinforced UF/MF membrane basin lining is not covered in this guide; contact ACC for a project-specific system (closest systems: PW-C1.1 / PW-C1.2).

CHEMICAL FEED & STORAGE BUILDINGS / SECONDARY CONTAINMENT


Secondary Containment Lining

Reinforced Novolac / Vinyl Ester Lining — Acid, Caustic, Oxidizer, Coagulant, Dechlorination, Organic

CMU / Concrete Walls

New CMU — Moderate/Heavy Duty, Chemical Resistant


New Concrete — Moderate/Heavy Duty, Chemical Resistant


Previously Painted CMU/Concrete — Moderate/Heavy Duty, Chemical Resistant


New CMU — Moderate Duty, Water Based


Previously Painted CMU/Concrete — Moderate Duty, Water Based


Exterior CMU/Concrete, Uncoated — Elastomeric / Crack-Bridging, Smooth Finish


Exterior CMU/Concrete, Previously Painted — Elastomeric / Crack-Bridging Recoat

Resinous Flooring (Building Floor, Outside Containment)

Urethane Cement — 1/4" Solid Color Urethane Cement — Heavy Duty

FILTER BUILDING / PROCESS GALLERIES & PIPING


Steel Pipe, Shop- or Field-Coated

Potable Water, Steel — Steel Pipe — Exterior, Non-Immersion


Potable Water, Steel — Steel Pipe — Immersion


Potable Water, Steel — Ductile Iron Pipe, Valves and Fittings — Exterior, Non-Immersion

Galvanized Pipe & Miscellaneous Fabrications

Galvanized Steel — New or Full Coating Removal, Urethane Finish (Good)


Galvanized Steel — Previously Coated Galvanized, Overcoat


New Steel — Galvanized Steel, Epoxy Finish


New Steel — Galvanized Steel, Urethane Finish


Previously Painted Steel — Galvanized Steel, Epoxy Finish


Previously Painted Steel — Galvanized Steel, Urethane Finish

Insulated Pipe (Jacketing)

Insulated Pipe Jacketing (Canvas / PVC Jacket)

PVC Pipe

PVC Pipe, Trim and Plastic Components

Resinous Flooring (Gallery / Tunnel Floor)

Urethane Cement — 1/8" Solid Color Urethane Cement — Moderate/Heavy Duty

EXTERIOR TANKS, EQUIPMENT & STRUCTURAL STEEL (SITE-WIDE)


Structural Steel, Tanks, Pipes & Equipment

Potable Water, Steel — Tanks, Structural Steel and Equipment — Exterior, Non-Immersion


Exterior New Steel — Zinc / Epoxy / Urethane (Good)


Exterior Steel Overcoat — Epoxy Mastic / Urethane (Good)

Condensation-Prone Metal (Chilled Lines, Enclosures)

Aerogel Insulative Coating on Steel Pipe, Tanks and Structure


Aerogel Thermal-Break Coating at Steel Envelope Penetrations

Resinous Deck Coating (Elevated Walkways & Platforms)

The elevated/exterior pedestrian deck coating (System WP1.1) is in the companion Resinous Flooring guide (Section 09 67 23).

INTERIOR / EXTERIOR SUPPORT BUILDINGS (UTILITY & MECHANICAL ROOMS)


Interior Structural Steel (Non-Immersion)

New Steel — Moderate Duty, Solvent Based Epoxy


New Steel — Moderate Duty, Solvent Based Epoxy w/ Urethane Finish


Previously Painted Steel — Moderate Duty, Solvent Based Epoxy Finish


Previously Painted Steel — Moderate Duty, Solvent Based Epoxy w/ Urethane Finish

Interior CMU / Concrete Walls

New CMU — Moderate Duty, Water Based


New CMU — Moderate Duty, Solvent Based


New CMU — Moderate/Heavy Duty, Water Based w/ Urethane Finish


New CMU — Moderate/Heavy Duty, 100% Solids Epoxy w/ Urethane Finish


New Concrete — Moderate Duty, Water Based


New Concrete — Moderate/Heavy Duty, Water Based w/ Urethane Finish


Previously Painted CMU/Concrete — Moderate Duty, Water Based


Previously Painted CMU/Concrete — Moderate/Heavy Duty, Water Based w/ Urethane Finish


Previously Painted CMU/Concrete — Moderate/Heavy Duty, 100% Solids Epoxy w/ Urethane Finish


Concrete Ceilings — Dry-Fall, High-Moisture / Natatorium Ceilings

Resinous Flooring (Mechanical Room Floor)

Urethane Cement — 1/4" Solid Color Urethane Cement — Heavy Duty

Water Treatment Plant Coating Systems

Includes water-specific systems (PW-S1, PW-C1), shared process systems (WW-C2, WW-S3) and the shared interior, exterior and resinous flooring systems from Sections 09 96 00 and 09 67 23. System codes are ACC's standard system codes and match Section 09 96 24.

Condition

Typical Locations

Surface Preparation

Coat Schedule (Product — DFT)

Total Build

WATER-SPECIFIC SYSTEMS — POTABLE WATER IMMERSION (NSF/ANSI/CAN 61) AND TANK EXTERIORS





PW-S1 — STEEL AND DUCTILE IRON — POTABLE WATER SYSTEMS


Note: NSF/ANSI/CAN 61 certified products are required for surfaces in contact with potable water. Exterior and non-immersion systems (PW-S1.3, PW-S1.6, PW-S1.7) do not require NSF/ANSI/CAN 61 certification.





Tanks, Structural Steel and Equipment — Immersion, 100% Solids Epoxy (Best)


PW-S1.1

Interior of steel potable water storage tanks, standpipes, elevated tanks, clearwell steel and immersed structural steel and equipment (best; 100% solids)

SSPC-SP10/NACE No. 2 Near-White Metal Blast Cleaning

Primer: Series 93-H2O Hydro-Zinc — 2.5–3.5 mils DFT


Stripe Coat: Series 21 Epoxoline — 4.0–6.0 mils DFT


Finish Coat: Series 22 / FC22 Epoxoline — 20.0–30.0 mils DFT


Note: NSF/ANSI/CAN 61 certification of Series 22 applies only to colors 22-WH11, 22-1218 and 22-1255.

22.5–33.5 mils DFT (excludes stripe coats)

Tanks, Structural Steel and Equipment — Immersion, High Solids Epoxy (Good)


PW-S1.2

Interior of steel potable water storage tanks, standpipes, elevated tanks and immersed steel and equipment (good; high solids)

SSPC-SP10/NACE No. 2 Near-White Metal Blast Cleaning

Primer: Series 93-H2O Hydro-Zinc — 2.5–3.5 mils DFT


Stripe Coat: Series 21 Epoxoline — 3.0–5.0 mils DFT


Finish Coat: Series 21 Epoxoline — 12.0–14.0 mils DFT

14.5–17.5 mils DFT (excludes stripe coats)

Tanks, Structural Steel and Equipment — Exterior, Non-Immersion


PW-S1.3

Exterior of steel water storage tanks, standpipes and elevated tanks, exposed structural steel, pipe supports and equipment in atmospheric service

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Primer: Series 93-H2O Hydro-Zinc — 2.5–3.5 mils DFT


Stripe Coat: Series 21 Epoxoline — 4.0–6.0 mils DFT


Intermediate Coat: Series 21 Epoxoline — 4.0–6.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 2.0–3.0 mils DFT

8.5–12.5 mils DFT (excludes stripe coats)

Steel Pipe — Immersion


PW-S1.4

Steel process and transmission piping in direct immersion contact with potable water — interior or exterior

SSPC-SP10/NACE No. 2 Near-White Metal Blast Cleaning

Primer: Series 21 Epoxoline — 4.0–5.0 mils DFT


Intermediate: Series 21 Epoxoline — 4.0–5.0 mils DFT


Finish Coat: Series 21 Epoxoline — 4.0–5.0 mils DFT


Note: NSF/ANSI/CAN 61 listings carry minimum pipe diameter and tank size limits; confirm the current Series 21 listing at www.nsf.org for the project.

12.0–15.0 mils DFT

Ductile Iron Pipe, Valves and Fittings — Immersion


PW-S1.5

Ductile iron pipe, valves and fittings in direct immersion contact with potable water — interior or exterior

Reference NAPF 500-03-04

Primer: Series 21 Epoxoline — 4.0–5.0 mils DFT


Intermediate: Series 21 Epoxoline — 4.0–5.0 mils DFT


Finish Coat: Series 21 Epoxoline — 4.0–5.0 mils DFT

12.0–15.0 mils DFT

Steel Pipe — Exterior, Non-Immersion


PW-S1.6

Exterior of exposed steel process piping in galleries, pump stations and yard piping, non-immersion

SSPC-SP6/NACE No. 3 (shop); lightly scarify shop coat, clean and dry (field)

Primer: Series 21 Epoxoline — 4.0–5.0 mils DFT


Intermediate: Series 21 Epoxoline — 4.0–5.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 2.0–3.0 mils DFT

10.0–13.0 mils DFT

Ductile Iron Pipe, Valves and Fittings — Exterior, Non-Immersion


PW-S1.7

Exterior of ductile iron pipe, valves and fittings in galleries, pump stations and yard piping, non-immersion

Reference NAPF 500-03-04

Primer: Series 21 Epoxoline — 4.0–5.0 mils DFT


Intermediate: Series 21 Epoxoline — 4.0–5.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 2.0–3.0 mils DFT

10.0–13.0 mils DFT

PW-C1 — CONCRETE — POTABLE WATER IMMERSION (NSF/ANSI/CAN 61 & 600)





Cast-in-Place Concrete — 100% Solids Epoxy (Best)


PW-C1.1

Cast-in-place or precast concrete clearwells, filter structures, finished/potable water storage basins and process structures in direct immersion contact with potable water

SSPC-SP13/NACE No. 6, ICRI-CSP 5 or greater

Surfacer / Filler (1/4"–4"): Series 217 MortarCrete — Applied at coverage rate


Surfacer / Filler (1/8"–1"): Series N218 MortarClad — Applied at coverage rate


Primer: Series 21 Epoxoline — 4.0–6.0 mils DFT


Finish Coat: Series 22 / FC22 Epoxoline — 20.0–30.0 mils DFT


Note: NSF/ANSI/CAN 61 certification of Series 22 applies only to colors 22-WH11, 22-1218 and 22-1255.

24.0–36.0 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Cast-in-Place Concrete — High Solids Epoxy (Good)


PW-C1.2

Cast-in-place or precast concrete clearwells, filter structures, finished/potable water storage basins and process structures in direct immersion contact with potable water (high-solids epoxy alternate)

SSPC-SP13/NACE No. 6, ICRI-CSP 3 or greater

Surfacer / Filler (1/4"–4"): Series 217 MortarCrete — Applied at coverage rate


Surfacer / Filler (1/8"–1"): Series N218 MortarClad — Applied at coverage rate


Primer: Series 21 Epoxoline — 4.0–6.0 mils DFT


Finish Coat: Series 21 Epoxoline — 12.0–14.0 mils DFT

16.0–20.0 mils DFT (over surfacer/filler applied as needed — not a rated coat)

WW-C2 — SECONDARY CONTAINMENT (CHEMICAL-SPECIFIC)





Reinforced Novolac / Vinyl Ester Lining — Acid, Caustic, Oxidizer, Coagulant, Dechlorination, Organic


WW-C2.1

Concrete secondary containment areas, sumps and curbs at chemical storage and feed systems — acids, caustic, oxidizers (hypochlorite), coagulants, dechlorination and organic chemicals

SSPC-SP13/NACE No. 6, ICRI-CSP 3-5; clean and dry

Block Filler (CMU only): Series 130 Envirofill — 60–80 SF/gal


Cant Cove: Trowelable lining at floor-to-wall transitions — Embedded wet (not rated)


Primer: Series 201 Epoxoprime — 6.0–8.0 mils DFT


Base Coat: Series 239SC ChemBloc — 8.0–12.0 mils DFT


Reinforcement: 3/4-oz fiberglass mat — Embedded wet (not rated)


Saturant: Series 239SC ChemBloc — 16.0–18.0 mils DFT


Finish Coat: Series 282 Tneme-Glaze — 6.0–8.0 mils DFT

36.0–46.0 mils DFT (over block filler applied at coverage rate)

WW-S3 — CONDENSATION MITIGATION / THERMAL INSULATING COATING





Aerogel Insulative Coating on Steel Pipe, Tanks and Structure


WW-S3.1

Metal surfaces subject to surface condensation — chilled/finished-water piping, enclosed damp or humid process spaces

SSPC-SP15 minimum (SSPC-SP6 preferred)

Primer: Series 394 PerimePrime — 2.5–3.5 mils DFT


First Coat: Series 971 Aerolon — 40.0–50.0 mils DFT


Intermediate: Series 971 Aerolon — 40.0–50.0 mils DFT


Finish Coat: Series 971 Aerolon — 40.0–50.0 mils DFT


Topcoat (exposed to view): Series 1028 Enduratone — 2.0–3.0 mils DFT

124.5–156.5 mils DFT

C1 — NEW OR PREVIOUSLY UNCOATED CMU





Moderate Duty, Water Based


C1.2

New or previously unpainted interior concrete/CMU walls — non-immersion process and support areas

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Block Filler: Series 130 Envirofill — 60–80 SF/gal


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT

8.0–12.0 mils DFT (over block filler applied at coverage rate)

Moderate Duty, Solvent Based


C1.3

Mechanical/electrical rooms, workshops, garages, storage and service areas where a solvent-based epoxy finish is acceptable and low odor is not required

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Block Filler: Series 130 Envirofill — 60–80 SF/gal


First Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT

8.0–12.0 mils DFT (over block filler applied at coverage rate)

Moderate/Heavy Duty, Water Based w/ Urethane Finish


C1.4

Locker rooms, restrooms, kitchens, corridors, custodial and service areas needing a scrubbable, color-retentive urethane finish over low-odor epoxy

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Block Filler: Series 130 Envirofill — 60–80 SF/gal


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.0–9.0 mils DFT (over block filler applied at coverage rate)

Moderate/Heavy Duty, 100% Solids Epoxy w/ Urethane Finish


C1.5

Laboratories, kitchens, washdown rooms, corridors and high-abuse areas where a 100% solids epoxy build and urethane finish are required

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Block Filler: Series 1254 Epoxoblock WB — ~100 SF/gal (CMU)


First Coat: Series 280 Tneme-Glaze — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.0–9.0 mils DFT (over block filler applied at coverage rate)

Moderate/Heavy Duty, Chemical Resistant


C1.6

Chemical storage and feed rooms (non-immersion), laboratories, battery rooms, wash bays and areas subject to chemical splash or frequent washdown

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Block Filler: Series 130 Envirofill — 60–80 SF/gal


First Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Finish Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT

8.0–12.0 mils DFT (over block filler applied at coverage rate)

Heavy Duty / Washdown, 100% Solids Reinforced


C1.7

High-traffic corridors, secure or controlled-access areas, maintenance/service spaces, wet areas, laboratories and walls subject to repeated impact or abuse

Clean and dry; allow new CMU and mortar to cure a minimum of 28 days; remove efflorescence, loose mortar and dust

Filler: Series 215 Surfacing Epoxy — 25–40 SF/gal


Glass Mat: Series 273 ML Stranlok, embedded into wet Series 215 — Embedded wet


Saturant: Series 280 Tneme-Glaze — 8.0–10.0 mils DFT


Intermediate: Series 280 Tneme-Glaze — 6.0–8.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

16.0–21.0 mils DFT (over surfacer/filler applied as needed — not a rated coat)

C2 — NEW OR PREVIOUSLY UNCOATED CONCRETE





Moderate Duty, Water Based


C2.2

Basements, utility rooms, service corridors, mechanical rooms and general interior poured or precast concrete walls in occupied facilities

SSPC-SP13/NACE No. 6 Surface Preparation of Concrete; ICRI-CSP 2-3; clean, dry, cured a minimum of 28 days

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate Duty, Solvent Based


C2.3

Mechanical/electrical rooms, workshops, garages, service and process support areas with interior concrete walls where low odor is not required

SSPC-SP13/NACE No. 6 Surface Preparation of Concrete; ICRI-CSP 2-3; clean, dry, cured a minimum of 28 days

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, Water Based w/ Urethane Finish


C2.4

Locker rooms, restrooms, kitchens, corridors and frequently cleaned interior concrete walls needing a urethane finish

SSPC-SP13/NACE No. 6 Surface Preparation of Concrete; ICRI-CSP 2-3; clean, dry, cured a minimum of 28 days

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.7–10.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, 100% Solids Epoxy w/ Urethane Finish


C2.5

Laboratories, washdown rooms, process support spaces and high-abuse interior concrete walls requiring a 100% solids epoxy build and urethane finish

SSPC-SP13/NACE No. 6 Surface Preparation of Concrete; ICRI-CSP 2-3; clean, dry, cured a minimum of 28 days

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 280 Tneme-Glaze — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.7–10.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, Chemical Resistant


C2.6

Chemical rooms (non-immersion), laboratories, wash bays and interior concrete walls subject to chemical splash or frequent washdown

SSPC-SP13/NACE No. 6 Surface Preparation of Concrete; ICRI-CSP 2-3; clean, dry, cured a minimum of 28 days

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Finish Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

C3 — EXISTING / PREVIOUSLY PAINTED CMU AND CONCRETE





Moderate Duty, Water Based


C3.2

Previously painted corridors, restrooms, break rooms, utility and service areas receiving a low-odor epoxy maintenance coating

SSPC-SP1; remove chalk/loose paint, patch cracks, spot prime bare areas, dull glossy surfaces

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate Duty, Solvent Based


C3.3

Previously painted mechanical rooms, workshops, garages and service areas where a solvent-based epoxy recoat is acceptable

SSPC-SP1; remove chalk/loose paint, patch cracks, spot prime bare areas, dull glossy surfaces

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, Water Based w/ Urethane Finish


C3.4

Previously painted locker rooms, restrooms, kitchens, corridors and frequently cleaned walls needing a urethane finish

SSPC-SP1; remove chalk/loose paint, patch cracks, spot prime bare areas, dull glossy surfaces

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 288/289 Enviro-Pox — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.7–10.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, 100% Solids Epoxy w/ Urethane Finish


C3.5

Previously painted laboratories, washdown rooms and high-abuse walls requiring a 100% solids epoxy build and urethane finish

SSPC-SP1; remove chalk/loose paint, patch cracks, spot prime bare areas, dull glossy surfaces

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 280 Tneme-Glaze — 4.0–6.0 mils DFT


Finish Coat: Series 297 Enviro-Glaze — 2.0–3.0 mils DFT

6.7–10.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

Moderate/Heavy Duty, Chemical Resistant


C3.6

Previously painted chemical rooms (non-immersion), laboratories, wash bays and walls subject to chemical splash or washdown

SSPC-SP1; remove chalk/loose paint, patch cracks, spot prime bare areas, dull glossy surfaces

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


Filler (as needed): Series 215 Surfacing Epoxy — Applied at coverage rate


First Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Finish Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT

8.7–13.5 mils DFT (over surfacer/filler applied as needed — not a rated coat)

C4 — CONCRETE CEILINGS – NEW, EXISTING PAINTED OR STRUCTURAL, PLANK AND DECK





Dry-Fall, High-Moisture / Natatorium Ceilings


C4.1

Pool or aquatic areas, high-humidity mechanical rooms, laundry areas, wash bays, wet-process rooms and persistently humid interior spaces

SSPC-SP13/NACE No. 6; clean and dry; remove loose/peeling coating on previously painted ceilings

Primer: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT


Intermediate: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT


Finish Coat: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT

6.0–12.0 mils DFT

Flexible / Mildew-Resistant Ceilings (Locker Rooms)


C4.2

Locker rooms, showers, laundry rooms, restrooms, wash areas and intermittently humid interior spaces

SSPC-SP13/NACE No. 6; clean and dry; remove loose/peeling coating on previously painted ceilings

Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


First Coat: Series 158 Bio-Lastic — 6.0–7.0 mils DFT


Finish Coat: Series 158 Bio-Lastic — 6.0–7.0 mils DFT

12.7–15.5 mils DFT

S1 — NEW OR PREVIOUSLY UNCOATED STEEL





Moderate Duty, Solvent Based Epoxy


S1.2

Structural steel, columns, beams, equipment supports, platforms and miscellaneous steel in mechanical rooms, garages, shops and process support areas

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


Touch-Up Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


First Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Note: Specify Series 90-97 Tneme-Zinc for natatorium and/or wet environments.

10.5–15.5 mils DFT (excludes touch-up coats)

Moderate Duty, Solvent Based Epoxy w/ Urethane Finish


S1.3

Exposed structural steel, stairs, railings, mezzanines and equipment in lobbies, gymnasiums, corridors and other visible interior spaces needing color and gloss retention

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


Touch-Up Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


First Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Note: Specify Series 90-97 Tneme-Zinc for natatorium and/or wet environments.


Note: Use Series 1090 as the finish coat for high traffic areas

9.5–13.5 mils DFT (excludes touch-up coats)

Heavy Duty, Chemical Resistant Epoxy


S1.4

Steel in chemical rooms, laboratories, wash bays and process areas subject to chemical splash, fumes or frequent washdown (non-immersion)

SSPC-SP10/NACE No. 2 Near-White Metal Blast Cleaning

Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


Touch-Up Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


First Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Stripe Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Finish Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT

10.5–15.5 mils DFT (excludes stripe/touch-up coats)

Overhead Structural Steel / Joists / Deck, Dry-Fall


S1.5

Overhead structural steel, bar joists, metal deck, ductwork and conduit in gymnasiums, warehouses, shops and open-ceiling spaces (dry-fall application)

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


Touch-Up Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


First Coat: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT


Finish Coat: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT


Note: Specify Series 90-97 Tneme-Zinc for natatorium and/or wet environments.

6.5–11.5 mils DFT (excludes touch-up coats)

Galvanized Steel, Epoxy Finish


S1.6

Galvanized pipe, handrails, ladders and miscellaneous fabrications — interior, non-immersion service

SSPC-SP1 to remove oil/grease/contaminants; SSPC-SP16 to remove storage stains and uniformly profile

First Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

Galvanized Steel, Urethane Finish


S1.7

Galvanized pipe, handrails, ladders and miscellaneous fabrications needing color and gloss retention — interior, non-immersion service

SSPC-SP1 to remove oil/grease/contaminants; SSPC-SP16 to remove storage stains and uniformly profile

First Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

Galvanized Steel, Light Architectural Duty


S1.8

Railings, stairs, ladders, supports, equipment frames, guards and miscellaneous galvanized or nonferrous metal

SSPC-SP1 to remove oil/grease/contaminants; SSPC-SP16 to remove storage stains and uniformly profile

Primer: Series 116 Uni-Bond — 2.0–4.0 mils DFT


Finish Coat: Series 1028 Enduratone — 2.0–3.0 mils DFT

4.0–7.0 mils DFT

S2 — EXISTING / PREVIOUSLY PAINTED STEEL





Moderate Duty, Solvent Based Epoxy Finish


S2.2

Previously painted structural steel, equipment supports, platforms and miscellaneous steel in mechanical rooms, garages, shops and process support areas

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning to degloss; remove loose coatings; feather transition edges

Spot Prime: Series 135 Chembuild — 4.0–6.0 mils DFT


First Coat: Series 135 Chembuild — 4.0–6.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT

8.0–12.0 mils DFT (excludes spot-prime coats)

Moderate Duty, Solvent Based Epoxy w/ Urethane Finish


S2.3

Previously painted exposed steel, stairs, railings and equipment in visible interior spaces needing color and gloss retention

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning to degloss; remove loose coatings; feather transition edges

Spot Prime: Series 135 Chembuild — 4.0–6.0 mils DFT


First Coat: Series 135 Chembuild — 4.0–6.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Note: Use Series 1090 as the finish coat for high traffic areas

7.0–10.0 mils DFT (excludes spot-prime coats)

Heavy Duty, Chemical Resistant Epoxy


S2.4

Previously painted steel in chemical rooms, laboratories, wash bays and process areas subject to chemical splash or washdown (non-immersion)

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning; SSPC-SP11 to bare metal at corroded areas; feather transition edges

Touch-Up Primer: Series 1 Omnithane — 2.5–3.5 mils DFT


First Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT


Finish Coat: Series 104 H.S. Epoxy — 4.0–6.0 mils DFT

8.0–12.0 mils DFT (excludes touch-up coats)

Overhead Structural Steel / Joists / Deck, Dry-Fall


S2.5

Previously painted overhead structural steel, joists, deck, ductwork and conduit in open-ceiling spaces (dry-fall application)

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning to degloss; remove loose coatings; feather transition edges

Spot Prime: Series 135 Chembuild — 4.0–6.0 mils DFT


First Coat: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT


Finish Coat: Series 115 Uni-Bond DF — 2.0–4.0 mils DFT

8.0–14.0 mils DFT

Galvanized Steel, Epoxy Finish


S2.6

Galvanized pipe, handrails, ladders and miscellaneous fabrications — interior, non-immersion service

SSPC-SP1; SSPC-SP2/SP3 to degloss and remove loose coating; SSPC-SP16 at exposed galvanizing

First Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT


Finish Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

Galvanized Steel, Urethane Finish


S2.7

Galvanized pipe, handrails, ladders and miscellaneous fabrications needing color and gloss retention — interior, non-immersion service

SSPC-SP1; SSPC-SP2/SP3 to degloss and remove loose coating; SSPC-SP16 at exposed galvanizing

First Coat: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

Hollow Metal Doors, Frames, Railings — Moderate/Heavy Duty


S2.9

Lobbies, atriums, public areas, assembly spaces, garages, maintenance areas, exposed columns/beams and existing mechanical or support steel

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning to degloss; remove loose coatings; feather transition edges

Primer: Series 27 Typoxy — 3.0–4.0 mils DFT


Finish Coat: Series 1090 Endura-Shield — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

M1 — MISCELLANEOUS INTERIOR SUBSTRATES





PVC Pipe, Trim and Plastic Components


M1.2

PVC trim, piping, panels and miscellaneous plastic components requiring field coating

Solvent clean and dry; lightly sand with #150-200 sandpaper

First Coat: Series 1028/1029 Enduratone — 2.0–3.0 mils DFT


Finish Coat: Series 1028/1029 Enduratone — 2.0–3.0 mils DFT

4.0–6.0 mils DFT

Insulated Pipe Jacketing (Canvas / PVC Jacket)


M1.3

Interior insulated pipe jacketing throughout the treatment plant

Clean and dry

First Coat: Series 1026 Enduratone — 2.0–3.0 mils DFT


Finish Coat: Series 1026 Enduratone — 2.0–3.0 mils DFT

4.0–6.0 mils DFT

Interior Aluminum and Non-Ferrous Metal


M1.4

Railings, stairs, ladders, supports, equipment frames, guards and miscellaneous galvanized or nonferrous metal

SSPC-SP1; light abrasive sweep blast or uniformly sand to profile; avoid damaging/warping thin components

Primer: Series 116 Uni-Bond — 2.0–4.0 mils DFT


Finish Coat: Series 1028/1029 Enduratone — 2.0–3.0 mils DFT

4.0–7.0 mils DFT

EC1 — NEW OR PREVIOUSLY UNCOATED CMU AND CONCRETE





Elastomeric / Crack-Bridging, Smooth Finish


EC1.1

Exterior masonry/CMU, unpainted

SSPC-SP13/NACE No. 6; clean, dry, free of oil/grease/form-release agents; allow new concrete/CMU to cure min. 14 days; repair cracks per mfr procedure

Block Filler (CMU, as needed): Series 130 Envirofill — 60–80 SF/gal


Primer: Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


First Coat: Series 156 Enviro-Crete — 6.0–8.0 mils DFT


Finish Coat: Series 156 Enviro-Crete — 6.0–8.0 mils DFT

12.7–17.5 mils DFT (over block filler applied at coverage rate)

EC2 — EXISTING / PREVIOUSLY PAINTED CMU, BRICK AND CONCRETE





Elastomeric / Crack-Bridging Recoat


EC2.1

Building envelopes, exterior CMU/concrete walls, above-grade foundations, screen walls, retaining walls and masonry requiring crack-bridging or weatherproofing

Power wash; remove loose/peeling coating and chalk; clean and dry

Primer (as needed): Series 151-1051 Elasto-Grip FC — 0.7–1.5 mils DFT


First Coat: Series 156 Enviro-Crete — 4.0–6.0 mils DFT


Finish Coat: Series 156 Enviro-Crete — 4.0–6.0 mils DFT

8.0–12.0 mils DFT; optional Primer (as needed) 0.7–1.5

ES1 — NEW OR FULL-COATING-REMOVAL STEEL





Zinc / Epoxy / Urethane (Good)


ES1.1

New fabrication or full coating removal — exterior structural steel, tanks, pipe supports and equipment, non-immersion service

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Shop or Field Primer: Series 90-97 Tneme-Zinc — 2.5–3.5 mils DFT


Touch-Up Primer: Series 90G-1K97 Tneme-Zinc — 2.5–3.5 mils DFT


Intermediate: Series V69 Hi-Build Epoxoline II — 4.0–6.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Note: Use Series 1090 as the finish coat for high traffic areas

9.5–13.5 mils DFT (excludes touch-up coats)

ES2 — EXISTING / PREVIOUSLY PAINTED STEEL (OVERCOAT)





Epoxy Mastic / Urethane (Good)


ES2.1

Existing exterior steel with a sound coating — support steel, equipment, enclosures, fencing, gates, tank exteriors and miscellaneous steel receiving an overcoat

SSPC-SP2/SP3 Hand/Power Tool Cleaning; remove loose coating; feather transition edges

Spot Prime: Series 135 Chembuild — 4.0–6.0 mils DFT


Full Prime Coat: Series 135 Chembuild — 4.0–6.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Note: Use Series 1090 as the finish coat for high traffic areas

7.0–10.0 mils DFT (excludes spot-prime coats)

ES3 — GALVANIZED STEEL





New or Full Coating Removal, Urethane Finish (Good)


ES3.1

New or stripped exterior galvanized railings, ladders, pipe, fencing, gates, support poles and miscellaneous galvanized metal — non-immersion service

SSPC-SP1 to remove oil/grease/contaminants; SSPC-SP16 to remove storage stains and uniformly profile

Primer: Series V69 Hi-Build Epoxoline II — 3.0–4.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT

6.0–8.0 mils DFT

Previously Coated Galvanized, Overcoat


ES3.3

Previously coated exterior galvanized railings, ladders, doors and frames, fencing, gates, support poles and miscellaneous galvanized metal

Wash clean; SSPC-SP2/SP3 Hand/Power Tool Cleaning to degloss; remove loose coatings; feather transition edges

Spot / Prime Coat: Series 27 Typoxy — 3.0–4.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Optional Finish: Series 1070V Fluoronar — 2.0–3.0 mils DFT

6.0–8.0 mils DFT; Optional Finish 2.0–3.0

ES4 — ALUMINUM AND NON-FERROUS METAL





General


ES4.1

Louvers, screens, railings, architectural trim, frames, stairs/platforms and exposed aluminum components

Light abrasive sweep blast (SSPC-SP16), uniform angular profile 1.0-2.0 mils; avoid damaging/warping thin components

Primer: Series V69 Hi-Build Epoxoline II — 2.0–3.0 mils DFT


Intermediate: Series 1095 Endura-Shield — 2.0–3.0 mils DFT


Finish Coat: Series 1071 Fluoronar — 2.0–3.0 mils DFT

6.0–9.0 mils DFT

ES5 — HOLLOW METAL DOORS AND FRAMES





Hollow Metal Doors, Frames, Railings — Moderate/Heavy Duty


ES5.2

Hollow-metal doors, frames, access doors, service doors, overhead-door components and similar ferrous assemblies

Uniformly scarify to remove glaze/sheen (test patch required)

Primer: Series 27 Typoxy — 3.0–4.0 mils DFT


Finish Coat: Series 1095 Endura-Shield — 3.0–4.0 mils DFT


Note: Use Series 1090 as the finish coat for high traffic areas

6.0–8.0 mils DFT

EW1 — WOOD





Bare or Previously Painted


EW1.1

Doors, trim, millwork, paneling and exposed architectural wood

Clean and dry; sand smooth

Primer: Series V10 Tnemec Primer — 2.0–3.5 mils DFT


First Coat: Series 1028 Enduratone — 2.0–3.0 mils DFT


Finish Coat: Series 1028 Enduratone — 2.0–3.0 mils DFT

6.0–9.5 mils DFT

ESL1 — WATER REPELLENTS, SEALERS AND ANTI-GRAFFITI





Penetrating Silane/Siloxane Water Repellent


ESL1.1

Exterior concrete, precast, brick, block, stone, stucco and other absorptive masonry exposed to weather; clear penetrating water repellent with no film build

Per product surface-absorption test; clean, dry, free of efflorescence

Sealer: Series 633 Prime-A-Pell H2O (Tnemec) — or Tex-Cote Rainstopper 120/140 — N/A (penetrating sealer)

Not applicable — penetrating sealer, no measurable dry film thickness

E1 — 100% SOLIDS EPOXY SYSTEMS





1/16" Solid Color Epoxy Broadcast — Light Duty


E1.3

Public restrooms, locker/shower dry areas, stairwells, and other light/moderate-duty areas where a decorative finish is desired

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 3 minimum

Cove Base (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Primer: Series N222 Deco-Tread — 250–320 SF/gal


Broadcast Coat: Series N222 Deco-Tread with 30/50 silica sand — 80–100 SF/gal


Grout Coat: Series N222 Deco-Tread (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/16" system

1/8" Solid Color Epoxy Broadcast — Moderate Duty


E1.4

Public restrooms, locker/shower dry areas, stairwells, and other light/moderate-duty areas where a decorative finish is desired

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 3 minimum

Cove Base (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Primer: Series N222 Deco-Tread — 250–320 SF/gal


First Broadcast Coat: Series N222 Deco-Tread with 30/50 silica sand — 80–100 SF/gal


Second Broadcast Coat: Series N222 Deco-Tread with 30/50 silica sand — 80–100 SF/gal


Grout Coat: Series N222 Deco-Tread (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/8" system

WB1 — WATER-BASED EPOXY





1/16" Solid Color Epoxy Broadcast — Light Duty


WB1.3

Offices, administrative areas, low-traffic corridors, break rooms, multipurpose rooms and dry storage areas in occupied buildings or where low-odor application is required

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 2-3 minimum

Cove Base (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Primer: Series 288/289 Enviro-Pox — 250–320 SF/gal


Broadcast Coat: Series 288/289 Enviro-Pox with 30/50 silica sand — 80–100 SF/gal


Grout Coat: Series 288/289 Enviro-Pox (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/16" system

1/8" Solid Color Epoxy Broadcast — Moderate Duty


WB1.4

Corridors, common areas, break and dining areas, equipment rooms, storage and service areas in occupied buildings or where low-odor application is required

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 2-3 minimum

Cove Base (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Primer: Series 288/289 Enviro-Pox — 250–320 SF/gal


First Broadcast Coat: Series 288/289 Enviro-Pox with 30/50 silica sand — 80–100 SF/gal


Second Broadcast Coat: Series 288/289 Enviro-Pox with 30/50 silica sand — 80–100 SF/gal


Grout Coat: Series 288/289 Enviro-Pox (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/8" system

UC1 — URETHANE CEMENT SYSTEMS





1/4" Solid Color Urethane Cement — Heavy Duty


UC1.1

Filter building mechanical rooms, chemical feed buildings, maintenance shops, and loading/receiving areas — heavy-duty interior floor areas subject to thermal shock, mechanical abuse, or frequent washdown

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 5 minimum

Base / Broadcast Coat: Series N242 Ultra-Tread S with 30/50 aggregate — 37 SF/kit


Coving (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Grout Coat: Series N222 Deco-Tread (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/4" system

1/8" Solid Color Urethane Cement — Moderate/Heavy Duty


UC1.3

Below-grade pump station dry pits, piping galleries/tunnels, and other moderate/heavy-duty floor areas with elevated moisture vapor transmission (MVT) concerns

NACE No. 6/SSPC-SP13, shot-blast or mechanically abrade to ICRI-CSP 5 minimum

Coving (where required): Series N283, N222 or 288 epoxy with aggregate — Applied at coverage rate


Base / Broadcast Coat: Series N241 Ultra-Tread MVT with aggregate — 90 SF/kit


Grout Coat: Series N222 Deco-Tread (pigmented) — 160–200 SF/gal


Finish Coat: Series 248 Everthane with 821 Field Colorant — 500–600 SF/gal

Nominal 1/8" system

SPECIALTY SYSTEMS





X1 — SPECIALTY SYSTEMS





Aerogel Thermal-Break Coating at Steel Envelope Penetrations


X1.1

Structural steel members (W-shapes, HSS and deck) that penetrate the building envelope and need a thermal break to limit condensation

SSPC-SP6/NACE No. 3 Commercial Blast Cleaning

Primer: Series 394 PerimePrime — 2.5–3.5 mils DFT


Insulative Coating (2–3 coats by shape): Series 971 Aerolon — 40.0–50.0 per coat (2 coats W-shapes / 3 coats HSS & deck)


Finish (exposed to view): Series 1028 Enduratone — 2.0–3.0 mils DFT

82.5–153.5 mils DFT (per shape; 2 coats W-shapes, 3 coats HSS/deck) plus 2.0–3.0 mils finish where exposed

Where to Go Next

  • For CSI 3-part bid/construction language: Section 09 96 24, High-Performance Coatings and Linings (Water Treatment), or contact Atlantic Coating Consultants.

  • For the full architectural interior/exterior system set: Section 09 96 00, High-Performance Coatings, and the companion Architectural Short-Form System Reference Guide; for floors, Section 09 67 23 and the Resinous Flooring guide.

  • For wastewater immersion/splash/spill and H2S/MIC systems: use the companion Short-Form System Reference Guide for Wastewater Treatment Facilities.

  • For unlisted chemicals, conditions, substrates, or flooring requirements: contact Atlantic Coating Consultants.

Atlantic Coating Consultants | Wally Bates | atlantic@tnemec.com | 484-644-5303


Recent Posts